This device is a 10 ampere 3 pole din-rail mount circuit breaker.
This circuit breaker is used in lighting distribution system or motor distribution system for protecting overload and short-circuit in the system. The product is novel in structure, light in weight, reliable and excellent in performance. It has high breaking capacity, can trip quickly and it's installation uses with guide, it's case and items are adopted with high fire-retardant and shockproof plastics. The product, with long life, is mainly used in AC 50Hz/60Hz, single-pole 240V or two, three, four-pole 415V circuit for overload and short-circuit protection as well as for infrequent on-and-off switching electric equipment and lighting circuit in normal case.
Standards: GB 10963, IEC898, BS3871.1.
Specification:
Breaking capacity 6kA
Electrical life no less than 6000 times
Mechanical life (0-c)no less than 20000 times
Tropical trial Treatment 2(RH 95% at 5'C)
No. of poles: 1, 2, 3, 4P
Rated voltage 240V/415V AC
Rated current 6, 10, 16, 20, 25, 32, 40, 50, 63A
Frame class 63A
Rated frequency 50/60Hz
Making and breaking capacity 6000A (6~40A),4500A (50,63A)
Release type B,C,D
Poles 1,2,3,4P
Mechanical life 20000
Instantaneous release type: C type (5ln~10ln)
Sequence |
Release |
Test |
Start state |
Tripping |
Expected |
1 |
B,C,D |
1.13In |
Cold state |
t≤1h |
Not tripping |
2 |
B,C,D |
1.45In |
Start right after |
t<1h |
Tripping |
3 |
B,C,D |
2.55In |
Cold state |
1s<t<60s |
Tripping |
4 |
B |
3In |
Cold state |
t≤0.1s |
Not tripping |
5 |
B |
5In |
Cold state |